Oil Flow Meter Tokico 80mm are positive displacement type flow meter which are used in a wide variety of applications including measuring of boiler fuel oil and diesel oil, as well as for transaction for kerosene, light oil and heavy oil.

FEATURES Oil Flow Meter Tokico 80mm
Wide flow range and high accuracy
- The accuracy of these flow meter is within +-0.5% over a wide range of flow rates (max. range of 1:150 for heavy oil )
Compact design
- A positive displacement type flow meter can be used at relatively high rotating speeds making for compact design. In addition, the counter unit of these meter is compact yet easy -to read , and and construction.
Small pressure
- Because the pressure loss of these meters is low, it is possible to perform accurate measuring at the suction side of a pump as well as accurate measurement of high viscosity fluids.
An electrical transmitter unit attachable
- A micro switch of a reed switch type transmitter unit having simple construction and high reliability is available.
Excellent durability
- The simple construction of these meters makes for long term durability with virtually no degradation of accuracy.
FRP Type
- Suitable for large volume flow
- Employs roots rotors made of cast iron
- Roots rotors rotate without physical contact
- Extremely low pressure loss
- Accuracy remains unchanged over a long period of time
STANDARD SPESIFICATION
- Accuracy : +-0.5%(+-0.2% with FGBB Type)
- Flow range :
- Kerosene, Light Oil :
- 3.500~35,000 l/h
- 3,500~25,000 l/h
- 40,000 l/h
- A heavy oil :
- 600~40,000 l/h
- 600~35,000 l/h
- 45,000 l/h
- B,C Heavy oil :
- 300~40,000l/h
- 300~35,000l/h
- 45,000 l/h
- Kerosene, Light Oil :
- Max. working pressure : 10kgf/cm2
- Hydraulic test pressure : 20kgf/cm2
- Max. working temperature :
- For kerosene, Light oil & Heavy oil
80deg C FGB Type & 100deg C with FRO & FRP Type
- For kerosene, Light oil & Heavy oil
- Flange rating : JIS 10kgf/cm2
- Material :
- Body :
- Cast Iron
- Rotor :
- FRP Type : Cast Iron
- Body :
- Counter Unit :
- Integrating pointer and integrating counter ( a reset counter is also available)
- Electrical transmitter unit :
- Transmitter : FRP Type (S) & (F)
- Power supply : AC100V, 50/60Hz as standard
- Number of pulse : 0~5 PPS
- Output signal ;ON-OFF Contact
- Transmission cable : 2-wire cable with cab type
- Flow direction : Right-left
- Paint Color : Munsell 1.4PB3.1 1/2